| Parameter |
Specification |
|
Standards
|
IEC 60831-1/2, EN 60831-1/2, GB/T 12747.1-2-2017
|
|
Over-voltage
|
1.1 Un (8 h/24 h), 1.15 Un (30 min/24 h)
|
|
Over-current
|
2.0 × In (up to 4.0 × In customizable)
|
|
Rated Frequency
|
50/60 Hz
|
|
Capacitance Tolerance
|
0% ~ +5%
|
|
Test Voltage (Terminal–Terminal)
|
2.15 × Un (AC), 10 s
|
|
Test Voltage (Terminal–Case)
|
≤ 660 V: 3,000 V (AC), 1 min; > 660 V: 6,000 V (AC), 10 s
|
|
Surge Current
|
200 × In
|
|
Power Consumption
|
≤ 0.2 W/kvar
|
|
Service Life
|
210,000 h
|
|
Protection Rating
|
IP20
|
|
Temperature Class
|
-40°C (D-class) / +5°C
|
|
Relative Humidity
|
< 95%
|
|
Altitude
|
≤ 4,000 m
|
|
Protection Technology
|
Dry-type technology, internal overpressure disconnector technology, self-healing technology
|
|
Discharge Time
|
60–180 s (external discharge module, customizable)
|
|
Installation
|
Horizontal or vertical installation, torque 10 N·m
|