Rated Operating Voltage
|
AC210V±20%
|
AC400V±20%
|
AC400V±20%
|
AC690V±15%
|
|
Single Module Capacity
|
50kvar
|
30kvar, 50kvar
|
75kvar, 100kvar
|
100kvar
|
|
Operating Frequency
|
50Hz±5%
|
|
Response Time
|
≤5ms
|
|
System Efficiency
|
≥97.5%
|
|
Reactive Compensation Rate
|
≥99%
|
|
Operation Modes
|
Reactive Power, Harmonic Mitigation, and Unbalance (Freely combinable)
|
|
Installation Type
|
Wall-mounted / Drawer-type
|
Wall-mounted / Drawer-type
|
Wall-mounted / Drawer-type
|
Drawer-type
|
|
Parallel Capability
|
Supports parallel operation of multiple units with unequal capacities
|
|
Capacitor Control
|
Supports up to 144 steps of passive control
|
|
Communication
|
RS-485, Modbus-RTU protocol
|
|
Cooling Method
|
Forced-air cooling
|
|
Noise Level
|
≤60dB
|
≤60dB
|
≤60dB
|
≤65dB
|
|
Protection Rating
|
Standard IP20
|
|
Operating Altitude
|
≤ 2000 m
|
|
Ambient Temperature
|
-10℃ to +40℃ (2%/K automatic derating above limit)
|
|
Relative Humidity
|
Max. monthly average 90%, non-condensing (at monthly avg. min. 25℃)
|
|
Dimensions (W×D×H) (mm)
|
Wall-mounted: 500×570×235
|
Wall-mounted: 505×200×554;
Drawer: 500×550×190
|
Wall-mounted: 505×260×574;
Drawer: 500×570×235
|
Drawer: 500×600×270
|
|
Weight
|
37kg
|
31.5kg
|
37kg
|
68kg
|
|
Compliance Standard
|
DL/T 1216-2019 (Technical Specification for Low-voltage Static Var Generator)
|